MR52 — Downstream Reader Interface

Overview

The Mercury MR52 is a downstream reader interface module used to expand a Mercury panel with additional reader ports. It adds 2 readers and 4 supervised inputs per module. Typically used with an EP1502 or similar host controller to support additional doors without a full second panel.

SpecValue
Readers2 (Wiegand or OSDP)
Inputs4 supervised
Outputs2 relay
CommunicationRS-485 downstream from host panel
Power Input12VDC from host or separate supply

DIP Switches

The MR52 uses DIP switches to set its downstream RS-485 address relative to the host panel. Multiple MR52 modules can be chained from a single host.

AddressSW1SW2SW3SW4
1ONOFFOFFOFF
2OFFONOFFOFF
3ONONOFFOFF
4OFFOFFONOFF
5ONOFFONOFF
6OFFONONOFF
7ONONONOFF

Address 0 (all OFF) is not valid — each MR52 must have a unique address. SW5–SW8: Reserved — leave OFF.