MP1501 — Single Door Panel

Overview

The Mercury MP1501 is a single-door access control panel. It supports 1 door with 2 readers (in/out), 8 supervised inputs, and 4 relay outputs. Connects to a host controller (EP1502, EP2500, etc.) via RS-485.

SpecValue
Doors1
Readers2 (Wiegand or OSDP)
Inputs8 supervised
Outputs4 relay
CommunicationRS-485 to host controller
Power Input12–24VDC

DIP Switches

The MP1501 has an 8-position DIP switch bank used to set the RS-485 board address. The address determines which port on the host controller this panel communicates on.

AddressSW1SW2SW3SW4SW5–8
0OFFOFFOFFOFFOFF
1ONOFFOFFOFFOFF
2OFFONOFFOFFOFF
3ONONOFFOFFOFF
4OFFOFFONOFFOFF
5ONOFFONOFFOFF
6OFFONONOFFOFF
7ONONONOFFOFF

SW5–SW8: Reserved — leave OFF. Address 0 is typically not used in production (reserved for default/unconfigured).


Wiring Notes


Resources


Revision #1
Created 2026-04-07 14:55:36 UTC by Ryan Walsh